Rugged design Ultrasonic bulk meter for sale
NWM ULW is the ultrasonic water meter having the size from Dn50 to Dn200, designed and manufactured by NWM.
WORKING PRINCIPLES:
The sound wave that flows in the direction of the stream moves faster than the one that flows against the stream.
The transit times Tab (Transit time of ultrasonic waves from sensor A to sensor B) and Tba (from sensor B to A) are measured continuously. The time difference (Tba - Tab) is directly proportional to the mean flow velocity (Vm) of the liquid. The flow rate is a result of the velocity multiplied by the cross section area of the flow tube size.
CHARACTERITICS:
No moving parts permitting the most reliable and longer term life; lowest pressure loss;
Battery life: ≥4years; possible to keep the external Battery bag for easy to exchange;
AMR ready for RS485, M-BUS...;
Digital Display:
m3: UNIT of Volume; m3/h: UNIT of Flow Rate
: Flow Direction
: Lower Battery
: Warning Signal
…
Keeping a magnet on the LCD at “LEFT- DOWN” location for at least 3 seconds, for changing menu from “member menu” to “Calibration menu”;
With rectifying device
DIMENSION:
The Flange Standard under ISO 7005-2:1998(E) PN10 as:
Dn |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
L |
200 |
|
225 |
250 |
|
300 |
350 |
H |
178 |
|
197 |
215 |
|
273 |
328 |
W |
160 |
|
196 |
215 |
|
282 |
340 |
D |
160 |
|
196 |
220 |
|
285 |
340 |
D1 |
125 |
|
160 |
180 |
|
240 |
295 |
nxM |
4xM16 |
8xM16 |
|
8xM20 |
Different Flange Standard for selecting such as: ISO 7005-2: 1998(E) PN16, ASME B16.1-Class 125 working for B16.5-Class 150…
Main Technical Data: ISO 4064 Class B
Size |
mm |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
|
R |
Q3/Q1 |
200 |
|||||||
Q4 |
m3/h |
50 |
78,75 |
125 |
312,5 |
500 |
|||
Q3 |
m3/h |
40 |
63 |
100 |
250 |
400 |
|||
Q2 |
m3/h |
0,32 |
0,504 |
0,8 |
2 |
3,2 |
|||
Q1 |
m3/h |
0,2 |
0,315 |
0,5 |
1,25 |
2 | |||
Max. Reading |
m3 |
9999999,9 |
|||||||
Min. Reading |
m3 |
0,0001 |
|||||||
Max. Pressure |
Bar |
MAP16 |
|||||||
Max. Temperate |
℃ |
T30 or T50 |
(For different Q3 and R, please contact with NWM manufacture).
MAX PERMISSION ERROR:
FOR CLASS I:
From Q1 inclusive up to but excluding Q2 is ± 1%; From Q2 inclusive up to and including Q4 is ± 3%; FOR CLASS II:
From Q1 inclusive up to but excluding Q2 is ± 2%; From Q2 inclusive up to and including Q4 is ± 5%;
Suggest to install the ULW water meter at U15 D5 (Straight pipe before the water meter at
15D, after the water meter at 5D);
Suggest to install the same size of the FILTER before the water meter;
Only for Horizontal installation;
OUTPUT for calibration:
1=>VCC (DC5~12V) – RED (POWER +)
2=>NC;
3=> Pulse Signal Output (DC 0~5V) - YELLOW 4=>GND – BLUE (POWER -)